Page 5 - 'Slimline' Outdoor Condensing Units - Frascold Models
P. 5
SH1/SL1 - QH1/QL1 Frascold Models
Application Notes …………
The SH/SL & QH/QL series are designed to provide maximum flexibility for the applications engineer in terms of :-
** Refrigeration capacity,
** Noise emmissions,
** Ambient temperature,
** Condensing Unit size
** Compressor type and manufacturer
** Power supply (1phase or 3 phase)
** Condensing Unit Price
The data shown in this book is based on Housing size, Condenser size, Condenser fan speed, Condenser Air flow, and Noise
emmissions for the various compressor types. There is a cross over at the extremities of each housing size e.g. the
compressors fitted top end of the SH1 series are also included in the bottom end of the SH2 series in order to provide the
diversification to suite a wider range of applications.
Hermetic Overlap Example :
Refrigeration Capacity - Watts Evaporating Temperature oC
Condensing dB(A) Compressor Amb Low Temperature Medium Temperature High Temperature
Unit Model @10M Condenser oC -40
SH1-25-150 32 - -35 -30 -25 -20 -15 -10 -5 0 5 10
38 T/CAJ4519Z
SH2-35-175 AC03-4p 32 - - - 1372 1792 2240 2721 3228 3758 4305 4865
39 T/CAJ4519Z - - 15010 1965 2478 3048 3675 4358 5099 5895
AC06-4p
Scroll Overlap Example :
Refrigeration Capacity - Watts Evaporating Temperature oC
Condensing dB(A) Compressor Amb Low Temperature Medium Temperature High Temperature
Unit Model @10M Condenser oC
SH1-25-ZB15 32 -40 -35 -30 -25 -20 -15 -10 -5 0 5 10
36 ZB15KCE-551 -
SH2-35-ZB15 AC03-4p 32 - 1392 1756 2151 2631 3151 3710 4290 4906 5542
-
38 ZB15KCE-551 - 1540 1965 2443 3002 3622 4308 5187 5899 6770
AC06-4p
Frascold Overlap Example :
Refrigeration Capacity - Watts Evaporating Temperature oC
Condensing dB(A) Compressor Amb Low Temperature Medium Temperature High Temperature
Unit Model @10M Condenser oC -40
SH1-25-100-6 32 524 -35 -30 -25 -20 -15 -10 -5 0 5 10
36 A1-6Y
SH2-35-100-6 AC03-4p 32 549 754 1038 1371 1753 2181 2646 3149 3684 4246 -
38 A1-6Y 793 1099 1467 1899 2395 2950 3569 4249 4978 -
AC06-4p
The examples shown above are all based on 4 pole condenser fan speed. Capacities for 6 pole and EC condenser fan models
are also shown in the condensing unit capacity data pages of this booklet enabling the design engineer to select against a wide
range of design criteria.
For applications advice please contact a member of our technical team via the Order Line shown at the bottom of this page.
July 2014 Order Line : 01449 722274 5