Page 8 - Hermetic Condensing Units
P. 8

Hermetic Condensing Units

Factory Fitted Options - Specification :                           Oil Separator Heater :
                                                                   If a condensing unit with a fitted oil separator will be subject
HP/LP Switch :                                                     to low ambient conditions an oil separator heater should be
All condensing units in the RCS hermetic range are fitted as       fitted to avoid refrigerant condensation during compressor off
standard with an auto/auto switch pre-wired to the connection      cycle periods.
box of the condensing unit.
                                                                   Liquid line stub fitted with Drier and Sight Glass :
HP Fan Switch :                                                    This option includes a suitably sized liquid line drier and sight
This option is only available for twin fan units and will be pre-  glass piped to the liquid receiver outlet and terminated at the
wired to the condensing unit electrical box.                       extremity of the condensing unit base plate, sealed with a
                                                                   brazed copper end cap. All necessary supporting brackets
Fan Speed Controller :                                             and fixing are included.
Due to the fan motor design this option is not available for the
RCS50 and 75 models. This option can be applied to all other       Suction Line Stub :
models in the range to optimize the head pressure and              This option includes a suitably sized suction line connected
reduce the unit noise level during periods of low ambient or       to the compressor inlet and terminated at the extremity of the
low load requirements. When applied this option will be pre-       condensing unit base plate, sealed with a brazed copper end
wired and piped to the condensing unit.                            cap. This line includes a stainless steel vibration eliminator
                                                                   on all sizes, together with all the necessary brackets and
Mains Isolator :                                                   supports. These stubs will be insulated with class 'O' 1/2"
This option is applicable to the entire range and comprises a      wall nitrile rubber pipe insulation.
6 pole isolator which will isolate the incoming power supply
and the control circuit thereby making the unit safe to work       Metal Housing :
on.                                                                This range of metal housings can be applied to all units in
                                                                   the range no matter what other options are fitted. This allows
Mains Isolator, Contactor and overload:                            the condensing unit to be sited safely outside subject to the
This option involves to application of a compressor contactor      elements. Care should be taken to allow for sufficient air
and suitably sized overload together with a unit isolator.         circulation space when units are sighted close to buildings.

Crankcase Heater :                                                 HP/LP Gauges :
All units are fitted as standard with this option except the       This option includes a 63mm diameter suction and discharge
RCS50 & 75-HTZ and the RCS75 & 150-LTZ models The                  gauge permanently fitted to the unit. Gauges are marked
heaters for these units are an optional extra.                     with saturation temperatures for R404A, R134a and R22.

Oil Separator :
This option can be applied to all units in the range and comes
complete with a suitably sized oil separator with a manual
shut-off valve in the oil return line.
An optional oil return solenoid valve and an oil return line
sight glass can be fitted on request. All these components will
be mounted within the condensing unit footprint and piped
into the system. Also included is the additional oil charge
required due to the increased internal system volume.